Remote Temperature Sensor; Keypad Lock; Troubleshooting - Bryant TSTATBBP250-LA Installation, Start-Up And Service Instructions Manual

Tempsure commercial thermostat
Table of Contents

Advertisement

IX. REMOTE TEMPERATURE SENSOR
A remote temperature sensor is available to read the tem-
perature from a space. If a remote temperature sensor is
connected, the thermostat will ignore the reading of its in-
ternal sensor. When the thermostat is using a reading from
a remote sensor, the degree symbol above the tempera-
ture reading will blink.
X. KEYPAD LOCK
To prevent unauthorized use of the thermostat, the front
panel buttons can be disabled. To disable or lock the
PROBLEM
Display on thermostat not illuminated.
''Service Filter'' is displayed on thermostat.
Cooling will not energize.
Heating will not energize.
When using 4 wires (R,G,W,Y), the cooling equip-
ment tries repeatedly to turn on, but cannot. At
times the display dims or disappears.
When using 4 wires (R,G,W,Y), the heating equip-
ment tries repeatedly to turn on, but cannot. At
times the display dims or disappears.
When controlling a heat pump, heat comes on
during cooling cycle.
When calling for cooling, both heating and cool-
ing are energized.
When controlling a commercial heat pump unit,
unit runs in reverse or heating is always on.
Copyright 1998 Bryant Heating & Cooling Systems

TROUBLESHOOTING

For thermostat troubleshooting see Table 4 below.
Table 4 — Thermostat Troubleshooting
Check for 24 vac at the R terminal connection. Terminal R must be
connected for proper thermostat operation.
After the configured number of blower operating hours, the Service
Filter message will be displayed. This reminds the owner to re-
place the filter. Reset the Service Filter feature to reset the blower
operation timer to 0 hours.
Select COOL mode. Decrease cooling set point to 10 degrees be-
low room temperature. Check for 24 vac at Y1 terminal. If present,
thermostat is operating correctly and problem is with wiring or equip-
ment. If 24 vac is not present, replace the thermostat. Check for
Compressor Cycle per Hour Limit. Cooling may be locked out.
Select HEAT mode. Increase heating set point to 10 degrees above
room temperature. Check for 24 vac at W1/O/B terminal. If present,
thermostat is operating correctly and problem is with wiring or equip-
ment. If 24 vac is not present, replace the thermostat.
There is not enough power available. Connect a 270 ohm, 10 watt
power resistor at the air-conditioning equipment between terminals
W and C (non-heat pump applications only).
There is not enough power available. Connect a 270 ohm, 10 watt
power resistor at the air-conditioning equipment between terminals
Y and C (non-heat pump applications only).
Configure thermostat for heat pump operation (Table 2, Step 3).
The thermostat is configured for a heat pump. Configure the ther-
mostat for non-heat pump operation (Table 2, Step 3).
Commercial heat pumps require that Heat Pump Option on ther-
mostat is turned OFF.
Printed in U.S.A.
keypad, press and hold the Mode button. While holding
down the Mode button, press the UP and DOWN ARROW
buttons simultaneously. The ''Locked'' icon will appear on
the display.
The thermostat is unlocked by performing the same pro-
cedure. Press and hold the Mode button. While holding down
the Mode button, press the UP and DOWN ARROW but-
tons simultaneously. The ''Locked'' icon will be removed from
the display.
SOLUTION
CATALOG NO. 809-684

Advertisement

Table of Contents
loading

Table of Contents