Bryant 355MAV Installation, Start-Up, And Operating Instructions Manual page 40

Series h deluxe 4-way multipoise variable-capacity direct vent condensing gas furnace
Table of Contents

Advertisement

e. Find closest natural gas heat value and specific gravity in
Table 11.
f. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low- and high-heat
manifold pressure settings for proper operation.
EXAMPLE: (0—2000 ft altitude)
Heating value = 1050 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 45
Manifold pressure: 3.8-in. wc for high heat
* Furnace is shipped with No. 45 orifices. In this example,
all main burner orifices are the correct size and do not need
to be changed to obtain proper input rate.
g. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE; ALWAYS CHECK AND
VERIFY.
2. Adjust manifold pressure to obtain input rate.
a. Remove burner enclosure front.
NOTE: Manifold pressure MUST always be measured with the
burner box cover REMOVED.
b. Remove regulator seal caps that conceal adjustment
screws for low- and high-heat gas valve regulators. (See
Fig. 62.)
AIR CONDITIONING
TONS (12,000 BTU/HR)
1-1/2
2
2-1/2
3
3-1/2
4
5
6
X-INDICATES AN ALLOWABLE SELECTION.
1.6-in. wc for low heat
AIRFLOW
040,060 & 042080
(CFM)
525
700
875
1050
1225
1400
1750
2100
A/C OR CF AIRFLOW SELECTION CHART
MODEL
SIZE
040, 060,
DEF
525
042080
2
060080, 100 DEF
700
2
120
DEF
700
1.DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2.DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
Fig. 58—A/C or CF Airflow Selection Chart
Based on 350CFM/Ton
c. Turn setup switch SW1-2 on control center to ON
position. (See Fig. 32.) This keeps furnace locked in
low-heat operation.
d. Jumper R and W/W1 thermostat connections on furnace
control to start furnace.
e. Turn low-heat adjusting screw (3/32 hex Allen wrench)
counterclockwise (out) to decrease input rate or clock-
wise (in) to increase input rate.
NOTE: DO NOT set low-heat manifold pressure less than 1.3-in.
wc or more than 1.7-in. wc for natural gas. If manifold pressure is
outside this range, change main burner orifices to obtain manifold
pressure in this range.
CAUTION: DO NOT bottom-out gas valve regulator
adjusting screw. This can result in unregulated manifold
pressure and result in excess overfire and heat exchanger
failures.
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered drill bit of
correct size. Never redrill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.
f. Turn setup switch SW1-2 to OFF position after complet-
ing low-heat adjustment.
060080 & 100
MODEL
MODEL
X
X
X
X
X
X
X
X
X
X
X
BASED ON 350 CFM/TON
700
875
1050
1225
1225
1
875
1050
1225
1400
1750
875
1050
1225
1400
1750
2
—40—
120 MODEL
X
X
X
X
X
X
X
1225
1750
1
2100
1
A02335