Figure 4 - Bard EIFM-3C Installation Instructions Manual

Economizers with exhaust for use with bard 2-1/2 through 3 ton wall mount air conditioners and heat pumps produced in 2005 and later
Table of Contents

Advertisement

IMPORTANT: Position front lip of economizer under
front grille and on top of condenser partition. (See
Figure 3 inset.) This is important to ensure proper
drainage of any water entering damper assembly.
6. Mount mixed air thermistor to blower partition as
shown with screws provided. Bracket with sensor
installs on top of blower partition. Screws are
inserted from the underside. Route wires as shown
and secure with wire tie. Connect wires to
thermistor. (See Figures 2 & 3.)
7. Open unit control panel to gain access to unit low
voltage terminal block.
8. FOR LEFT HAND UNITS Reroute economizer
wiring harness to the left side. (See Figure 4.)
9. Route electrical harness leads through the 7/8"
bushing in control panel (Figure 5) into low voltage
box.

FIGURE 4

Manual 2100-449A
Page
7 of 13