Connecting to DC Power

Grounding the Switch

This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the
Warning
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection
authority or an electrician if you are uncertain that suitable grounding is available. Statement 1024
To make sure that the equipment is reliably connected to earth ground, follow the grounding procedure
Caution
instructions, and use a UL-listed lug suitable for number-6 AWG wire and two number-10-32
ground-lug screws.
To ground the switch to earth ground, follow these steps. Make sure to follow any grounding
requirements at your site.
Locate and remove the ground lug and the two number-10-32 ground-lug screws from the rear panel of
Step 1
the switch. (See
screwdriver with a Phillips head. Set the screws and the ground lug aside.
If your ground wire is insulated, use a wire stripping tool to strip the 6-gauge ground wire to 0.5
Step 2
inch (12.7 mm) ± 0.02 inch (0.5 mm), as shown in
Figure C-1
Step 3
Slide the open end of the ground lug over the exposed area of the 6-gauge wire.
Catalyst 3750 Switch Hardware Installation Guide
C-2
6-gauge copper ground wire (insulated or noninsulated)
Four leads of 18-gauge copper wire
Wire-stripping tools for stripping 6- and 18-gauge wires
Figure C-3
for location.) Use a standard Phillips screwdriver or a ratcheting torque
Stripping the Ground Wire
0.5 in. (12.7 mm) ± 0.02 in. (0.5 mm)
Insulation
Figure
C-1.
Wire lead
Appendix C
Connecting to DC Power
OL-6336-10