Gas Supply Line Purging And Sizing - A.O. Smith HW 300 Installation & Operation Manual

Gas-fired commercial copper boilers for hydronic heating and hot water supply up-flow models
Hide thumbs Also See for HW 300:
Table of Contents

Advertisement

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS
SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP
LEG or sediment trap) MUST BE INCORPORATED IN THE
PIPING, see Figure 1 on page 6. The dirt leg must be readily
accessible and not subject to freezing conditions. INSTALL IN
ACCORDANCE WITH RECOMMENDATIONS OF SERVING
GAS SUPPLIERS. (Refer to National Fuel Gas Code, ANSI
Z223.1 or CAN/CSA-B 149.1 Installation Codes.
To prevent damage, care must be taken not to apply too
much torque when attaching gas supply pipe to the gas valve
gas inlet.
Fittings and unions in the gas line must be the metal to
metal type.
Apply joint compounds (pipe dope) sparingly and only to the
male threads of pipe joints. Do not apply compound to the first
two threads. Use compounds resistant to the action of liquefied
petroleum gases.
THE BOILER AND ITS GAS CONNECTIONS MUST BE LEAK
TESTED BEFORE PLACING THE BOILER IN OPERATION.
Use soap and water solution or other material acceptable for
the purpose in locating gas leaks. DO NOT USE MATCHES,
CANDLES, FLAME OR OTHER SOURCES OF IGNITION FOR
THIS PURPOSE.
D I S C O N N ECT T H E B O I L ER A N D I T S M A I N M A N UA L
GAS SHUTOFF VALVE FROM THE GAS SUPPLY PIPING
SYSTEM DURING ANY PRESSURE TESTING OF THE GAS
SUPPLY SYSTEM OVER 1/2 PSIG (3.5kPa). THE GAS SUPPLY
LINE MUST BE CAPPED WHEN NOT CONNECTED TO
THE BOILER.
THE BOILER MUST BE ISOLATED FROM THE GAS SUPPLY
PIPING SYSTEM BY CLOSING ITS MAIN MANUAL GAS
SHUTOFF VALVE DURING ANY PRESSURE TESTING OF
THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES
EQUAL TO OR LESS THAN 1/2 PSIG (3.5kPa).
PURGING AND SIZING
Gas line purging is required with new piping or systems in which
air has entered.
P U R G I N G S H O U L D B E P E R F O R M E D B Y P E R S O N S
EXPERIENCED IN THIS TYPE GAS SERVICE TO AVOID RISK OF
FIRE OR EXPLOSION. PURGE DISCHARGE MUST NOT ENTER
CONFINED AREAS OR SPACES WHERE IGNITION CAN OCCUR.
THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF
IGNITION MUST BE INACTIVATED OR REMOVED.
1.
CORRECT GAS
Make sure the gas on which the boiler will operate is the same as
that specified on the boiler rating plate. Do not install the boiler if
equipped for a different type gas — consult your supplier.
2A. SIZING GAS SUPPLY LINE (For single boiler installations
and for installations of multiples of two or three of same
size boilers).
CAUTION
U s e t a b l e 7, o r C A N / C S A B14 9 .1 (c u r r e n t e d i t i o n) t o
s i ze i r o n p i p e o r e q u i va l e n t g a s s u p p l y l i n e. Ta b l e 7
is based on a pressure drop of 0.3 inches of water and
a specif ic gravit y of 0.6 0 approximately that of natural
gas. (LP gas has an S.G. of about 1.53). If the service pressure
is five inches water column or less, use one pipe size larger in
order to minimize pressure drop in the line.
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER
HOUR (BASED UPON A PRESSURE DROP OF 0.3 INCH
WATER COLUMN AND 0.6 SPECIFIC GRAVITY GAS)
Distance
Nominal Iron Pipe Size (Inches)
from Gas
Meter
1/2
3/4
1
10 (3)
132
278
520 1,050 1,600 3,050 4,800 8,500 17,500
20 (6)
92
190
350
30 (9)
73
152
285
40(12)
63
130
245
50 (15)
56
115
215
60 (18)
50
105
195
70 (21)
46
96
180
80 (24)
43
90
170
90 (27)
40
84
160
100 (30)
38
79
150
125 (38)
34
72
130
150 (45)
31
64
120
175 (53)
28
59
110
200 (60)
26
55
100
*The heating value of Natural Gas is approximately 1,050 Btu/Ft
Propane (LP) Gas has a heating value of approximately 2,500 Btu/Ft
1 cu. meter=35.31 cu. feet.
Where it is necessary to use more than the average number of pipe
fittings i.e. elbows, tees, and valves in gas supply line, use a pipe
larger than specified to compensate for increased pressure drop.
2B. SIZING GAS SUPPLY LINE (For multiples of over three boilers of
same size or for multiple installations of two or more mixed sizes).
Capacities in cubic feet per hour of 0.60 specific gravity gas for
different sizes and lengths are shown in table 7. No additional
allowance is necessary for an ordinary number of fittings.
Applications of the gravity factor converts the figures given in table
7 to capacities with another gas of different specific gravity. Such
application is accomplished by multiplying the capacities given in
table 7 by the multipliers shown in table 8 on page 22.
To determine the size of each section of gas piping in a system within
the range of table 7 proceed as follows:
Determine the gas demand of each appliance to be attached
to the piping system. When table 7 is to be used to select the
piping size, calculate the gas demand in terms of cubic feet
per hour for each piping system outlet. The gas demand for
an appliance can be found by dividing its heat input rate by
the gas's heating value.
Obtain or determine the length of piping from the gas meter or
service regulator to the appliance(s).
21
TABLE 7.
1 1/4 1 1/2
2
2 1/2
3
730 1,100 2,100 3,300 5,900 12,000
590
890
1,650 2,700 4,700 9,700
500
760
1,450 2,300 4,100 8,300
440
670
1,270 2,000 3,600 7,400
400
610
1,150 1,850 3,250 6,800
370
560
1,050 1,700 3,000 6,200
350
530
990
1,600 2,800 5,800
320
490
930
1,500 2,600 5,400
305
460
870
1,400 2,500 5,100
275
410
780
1,250 2,200 4,500
250
380
710
1,130 2,000 4,100
225
350
650
1,050 1,850 3,800
210
320
610
980
1,700 3,500
.
.3
.
3
4