LG LMCN125HV Instructions Manual page 29

Flex multi split
Hide thumbs Also See for LMCN125HV:
Table of Contents

Advertisement

Available languages

Available languages

5. Use the connecting cable to connect the indoor unit and the wired remote
controller.
6. When the distance between the wired remote controller and the indoor unit is
10m and above, use the extension cable.
CAUTION
When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
Do not install the cable to be 50m or above.
(It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote
controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
Check whether the connector
is connected correctly.
Connecting cable
Installation
Indoor
unit side
Installation Manual 29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents