Control And Switches; Blower Prover Switch; Blocked Outlet Prover Switch; Blocked Inlet Prover Switch - A.O. Smith SERIES 100 Installation & Operating Instructions Manual

Series 100 and 101 commercial gas water heater gas-fired power burner for domestic hot water
Hide thumbs Also See for SERIES 100:
Table of Contents

Advertisement

CONTROLS AND SWITCHES
All BTH models are provided with four pressure switches. These switches
are essential to the safe and proper operation of the unit. All switches are
wired in series. The controller is set up to shut the unit down whenever
there is a failure of any of the switches. It is important to understand the
purpose of each switch.

BLOWER PROVER SWITCH

(SEE FIGURE 12)
The Blower Prover Switch is provided on the heater to verify that the fan is
operating. It is a positive pressure switch whose electrical contacts are
normally open. When the fan increases the pressure in the burner, the
pressure switch will allow the electrical contacts to close. The pressure
switch is connected to the burner tap by a piece of tygon tubing. This
tubing must be connected in order for the switch to change the electrical
contacts. The controller requires that the electrical contacts on this air flow
switch be open before it will allow the blower to come on.

BLOCKED OUTLET PROVER SWITCH

(SEE FIGURE 12)
The Blocked Outlet Prover Switch is set up to shut the unit off when a build-
up of positive pressure in the exhaust vent pipe occurs. This switch is a
positive pressure switch that requires an increase in pressure to change
the electrical contacts from normally closed to open. When this switch
prevents the unit from igniting, most likely the exhaust is blocked by some
means Check to see if the condensate is allowed to flow freely from the
exhaust elbow and for obstructions in the exhaust venting and exhaust
vent terminal. Also verify that there is no more than fifty equivalent feet
(15.2 m) of three inch PVC vent pipe on the exhaust.

BLOCKED INLET PROVER SWITCH

(SEE FIGURE 12)
The Blocked Inlet Prover Switch is set up to shut the unit off when a build-
up of negative pressure in the intake vent pipe occurs. This switch is a
negative pressure switch that requires an increase in negative pressure to
change the electrical contacts from normally closed to open. The switch is
connected to the pressure tap on the PVC flange connected to the inlet of
the blower. When this switch prevents the unit from igniting, most likely the
intake is blocked by some means. Check to see if there is no more than fifty
equivalent feet (15.2 m) of three inch PVC vent pipe on the intake. Also
verify that the intake and intake vent terminal is free of obstructions that
may prevent air from entering the unit.
FIGURE 12.

LOW GAS PRESSURE SWITCH

The Low Gas Switch (LGS) is a single-pole, normally open pressure switch
that will close its contacts when a rising pressure of 5.0 in. (1.25Kpa) W.C.
is encountered. The contacts will open when the pressure falls below the
fixed set point of 4.8"WC (1.18Kpa) for natural gas models and 8.5"WC
(2.08Kpa) for propane models. The LGS monitors the gas supply pressure
to the heater. If the gas supply falls below 4.8"WC (1.18Kpa), the main
burner is extinguished (if heater is running) or the heater will not start up.

ON/OFF SWITCH

The ON/OFF Switch is a single-pole, single-throw rocker switch. This
switch provides 120V from the line source to the heater.
THE WATER HEATER IS POLARITY SENSITIVE. BEFORE APPLYING
ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY NEUTRAL WIRE
TO GROUND CHECK INDICATES ZERO VOLTAGE.

HOT SURFACE IGNITER

The Hot Surface Igniter is a device that ignites the main burner by high
temperature (>1800°F or >982°C). When 120VAC is applied to the igniter,
sufficient heat is generated to ignite the main burner. Although improvements
have been made to strengthen the igniter, it is still fragile and care must be
taken when handling the igniter to prevent breakage.

GAS PIPING

Contact your local gas service company to ensure that adequate gas
service is available and to review applicable installation codes for your
area.
Size the main gas line in accordance with Table 3. The figures shown are
for straight lengths of pipe at 0.5" (125Pa) W.C. pressure drop, which is
considered normal for low pressure systems Note that fittings such as
elbows and tees will add to the pipe pressure drop.
DO NOT USE FLEXIBLE GAS PIPING.
TABLE 3. MAXIMUM CAPACITY OF PIPE IN CUBIC FEET
OF GAS PER HOUR
(Based upon a Pressure Drop of 0.5") Water Column and 0.6
Specific Gravity Gas and max. gas pressure of 0.5 psig)
LENGTH
NORMAL IRON PIPE SIZES (INCHES)
IN
INPUT IN THOUSANDS BTU/HR
FEET
1/2"
3/4"
1"
10
175
360
680
20
120
250
485
30
97
200
375
40
82
170
320
50
73
151
285
60
66
138
260
70
61
125
240
80
57
118
220
90
53
110
205
100
50
103
195
125
44
93
175
150
40
84
160
175
37
77
145
200
35
72
135
LENGTH
NORMAL IRON PIPE SIZES (INCHES)
IN
METERS 1/2"
3/4"
1"
3.0
51
105
199
6.1
35
73
142
9.1
28
59
110
12.2
24
50
94
15.2
21
44
83
18.3
19
40
76
21.3
18
37
70
24.4
17
35
64
27.4
16
32
60
30.5
15
30
57
38.1
13
27
51
45.7
12
25
47
53.3
11
23
42
61.0
10
21
40
13
(SEE FIGURE 12)
CAUTION
CAUTION
1 1/4" 1 1/2"
2"
2 1/2"
3"
1400
2100
3960
6300
11000 23000
950
1460
2750
4360
7700
770
1180
2200
3520
6250
660
990
1900
3000
5300
580
900
1680
2650
4750
530
810
1520
2400
4300
490
750
1400
2250
3900
460
690
1300
2050
3700
430
650
1220
1950
3450
400
620
1150
1850
3250
360
550
1020
1650
2950
325
500
950
1500
2650
300
460
850
1370
2450
280
430
800
1280
2280
INPUT IN KW
1 1/4" 1 1/2"
2"
2 1/2"
3"
410
615
1160
1845
3221
278
428
805
1277
2255
225
346
644
1031
1830
193
290
556
878
1552
170
264
492
776
1391
155
237
445
703
1259
143
220
410
659
1142
135
202
381
600
1083
126
190
357
571
1010
117
182
337
542
952
105
161
299
483
864
95
146
278
439
776
88
135
249
401
717
82
126
234
375
688
4"
15800
12800
10900
9700
8800
8100
7500
7200
6700
6000
5500
5000
4600
4"
6735
4626
3748
3192
2840
2577
2372
2196
2108
1962
1757
1610
1464
1347

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents