AIR FOR COMBUSTION AND VENTILATION
6
Determining Fresh-Air Flow for Fireplace Location (Cont.)
Ventilation Air
AIR FOR COMBUSTION AND
VENTILATION
Continued
3.
Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fireplace
Gas water heater*
Gas furnace
Vented gas heater
Gas fireplace logs
Other gas appliances* + _____________ Btu/Hr
Total
* Do not include direct-vent gas appliances. Direct-vent draws com-
bustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater
Vent-free fireplace
Total
4.
Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support)
__________________ Btu/Hr (actual amount of Btu/Hr used)
Example: 35,840 Btu/Hr (maximum the space can support)
40,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See Ventilation Air From
Inside Building.
B.
Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 7.
C.
Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room
unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support,
the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the fireplace may
be operated is smaller than that defined as an uncon-
fined space or if the building is of unusually tight
construction, provide adequate combustion and ven-
tilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec-
tion 5.3 or applicable local codes .
For more information, visit www.desatech.com
For more information, visit www.desatech.com
_____________ Btu/Hr
_____________ Btu/Hr
_____________ Btu/Hr
_____________ Btu/Hr
_____________ Btu/Hr
= _____________ Btu/Hr
30,000
_____________ Btu/Hr
10,000
+ _____________ Btu/Hr
40,000
= _____________ Btu/Hr
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space.
When ventilating to an adjoining unconfined space, you must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 4). You can also remove door into
adjoining room (see option 3, Figure 4). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion
and Ventilation for required size of ventilation grills or ducts.
Ventilation
Grills
Into Adjoining
Or
Room,
Remove
Option 1
Door into
Adjoining
Room,
Option
3
12"
Figure 4 - Ventilation Air from Inside Building
12"
Ventilation Grills
Into Adjoining Room,
Option 2
111244-01A