Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1.
Close manual shutoff valve (see Fig-
ure 28).
2.
Pressurize supply piping system by ei-
ther opening propane/LP supply tank
valve for propane/LP gas fireplace or
opening main gas valve located on or near
gas meter for natural gas fireplace, or
using compressed air.
3.
Check all joints from propane/LP sup-
ply tank or gas meter to manual shutoff
valve (see Figure 29 for propane/LP or
Figure 30 for natural). Apply commer-
cial leak test solution to all gas joints.
Bubbles forming show a leak. Correct
all leaks at once.
Pressure Testing Fireplace Gas
Connections
1. Open manual shutoff valve (see Fig-
ure 28).
2.
Open propane/LP supply tank valve for
propane/LP fireplace or main gas valve
located on or near gas meter for natu-
ral gas fireplace.
3.
Make sure control knob of fireplace is
in the OFF position.
4. Check all joints from manual shutoff
valve to thermostat gas valve (see Fig-
ure 29 for propane/LP or Figure 30 for
natural). Apply commercial leak test so-
lution to all gas joints. Bubbles forming
show a leak. Correct all leaks at once.
5.
Light fireplace (see Lighting Instruc-
tions, page 18). Check all other inter-
nal joints for leaks.
6.
Turn off fireplace (see To Turn Off Gas
to Appliance, page 18).
®
Manual
Shutoff
Valve
Figure 28 - Manual Shutoff Valve
Gas Valve
Figure 29 - Checking Gas Joints for Propane/LP Gas Freestanding Fireplace
Gas Valve
Figure 30 - Checking Gas Joints for Natural Gas Freestanding Fireplace