Air For Combustion; Combustion And Ventilation Air - Desa LSF20NT Safety Information And Installation Manual

Unvented (vent-free) solar fusion gas heater
Table of Contents

Advertisement

Available languages

Available languages

AIR FOR COMBUSTION

AND VENTILATION
Continued
1.
Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (6.1 m) (length) x
16 ft. (4.88 m) (width) x 8 ft. (2.44 m) (ceiling
height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2.
Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (72.4 m
= 51,200 (maximum Btu/Hr the space can support)
3.
Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free heater
Gas water heater*
Gas furnace
Vented gas heater
Gas fireplace logs
Other gas appliances* + ____________ Btu/Hr
Total
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
Example:
Gas water heater
Vent-free heater
Total
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_________ Btu/Hr (maximum the space can support)
_________ Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space
can support)
60,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a confined space
because the actual Btu/Hr used is more than the maxi-
mum Btu/Hr the space can support. You must provide
additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconfined
space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 7.
6
) (volume of space) x 20
3
_____________ Btu/Hr
_____________ Btu/Hr
_____________ Btu/Hr
_____________ Btu/Hr
_____________ Btu/Hr
= ____________ Btu/Hr
40,000
_____________ Btu/Hr
20,000
+ ____________ Btu/Hr
60,000
= ____________ Btu/Hr
www.desatech.com
C. Install a lower Btu/Hr heater, if lower Btu/Hr size
makes room unconfined.
If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space is an un-
confined space. You will need no additional fresh
air ventilation.
WARNING: If the area in
which the heater may be oper-
ated is smaller than that defined
as an unconfined space or if the
building is of unusually tight
construction, provide adequate

combustion and ventilation air

by one of the methods described
in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un-
confined space. When ventilating to an adjoining
unconfined space, you must provide two perma-
nent openings: one within 12" (30.4 cm) of the
ceiling and one within 12" (30.4 cm) of the floor
on the wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
Ventilation
Grills
Or
into Adjoining
Remove
Room,
Door into
Option 1
Adjoining
Room,
Option 3
Figure 2 - Ventilation Air from Inside
Building
12"
Ventilation Grills
Into Adjoining Room,
Option 2
12"
116307-01B