Section 6: Power Supply Requirements

6.1 Overview

This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1.
Calculating the total amount of AC branch circuit current required to operate the system
2.
Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
3.
Calculating the size of batteries required to support the system if an AC power loss occurs
4.
Selecting the proper batteries for your system

6.2 Calculating the AC Branch Circuit

The power supply requires connection to a separate, dedicated AC branch circuit, which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed
of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm
branch circuit. The branch circuit wire must run continuously, without any disconnect devices,
from the power source to the power supply. Overcurrent protection for this circuit must comply
with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm2)
wire with 600 volt insulation for this branch circuit.
Use Table 6.1 to determine the total amount of current, in AC amperes, that must be supplied to the
system
Device Type
HPF24S6/8
HPF24S6/8E

6.3 Calculating the System Current Draw

6.3.1 Overview
The power supply must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the power supply when primary
power is applied, use Calculation Column 1 in Table 6.3 on page 40. The power supply must
support a larger load current during a fire alarm condition. To calculate the fire alarm load on the
power supply, use Calculation Column 2 in Table 6.3 on page 40. The secondary power source
(batteries) must be able to power the system during a primary power loss. To calculate the non-fire
alarm load on the secondary power source, use Calculation Column 3 in Table 6.3 on page 40.
When calculating current draw and the battery size, note the following:
Primary refers to the main power source for the power supply.
38
Number of
Devices
or
1
[
]
[
]
[
]
[
]
Sum Column for AC Branch Current Required
Table 6.1 120/240 VAC Branch Circuit Requirements
Current Draw
(AC amps)
3.2
X
or
1.6
X
[
]
X
[
]
HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
Total Current
per Device
=
3.2
=
=
=

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpf24s6Hpf24s6eHpf24s8eHpf24s6cHpf24s8c

Table of Contents