Special Application Auxiliary Power Control; 5: Charger Enable/Disable; 6: Door Closers - Honeywell HPF24S8 Installation Manual

Field charger/power supply
Hide thumbs Also See for HPF24S8:
Table of Contents

Advertisement

Programming Options
The following table details the four possible input/output configurations:
DIP Switch 5
DIP Switch 6
OFF
OFF
OFF
ON
ON
OFF
ON
ON
1
If Door Closer function is selected (switch 8 ON), Output 4 does not function as an NAC, therefore sync input is ignored for
Output 4.
2
If no synchronization is selected by switches 1 & 2, the Sync Input is ignored.
3
Selective Silence allows the silencing of the sounder portion of a horn/strobe combination device without turning off the strobe.
4
When using Split Alarm with power supply configured in Slave Mode, System Sensor can not be used (Use System Sensor with
Master Mode only)

Special Application Auxiliary Power Control

The 24 VDC Auxiliary power from TB4 Terminals 9(+) & 10(-) can be resettable or nonresettable
power only when the power supply is configured for General Alarm operation. For all other
configurations, the auxiliary power output is only nonresettable.
In the General Alarm configuration, the Auxiliary power output can be made resettable by applying
a steady signal to Control Input 2 (positive 12 to 24 VDC on TB4 Terminal 7 and common on
Terminal 8). Temporarily removing the voltage or reversing the polarity will cause the Auxiliary
power output to reset for 6 seconds.
3.2.5 Charger Enable/Disable
The HPF24S battery charger can be disabled to accommodate an external battery charger. Setting
DIP switch 7 to the default setting of OFF will enable the battery charger. Setting DIP switch 7 to
the ON position will disable the charger. It should only be disabled if an external battery charger is
being used for the HPF24S.
3.2.6 Door Closers
Output Circuit #4 can be configured as an NAC or door closer circuit. Setting DIP switch 8 to the
OFF position will configure Output Circuit #4 as an NAC. Setting DIP switch 8 to the ON position
will configure only Output Circuit #4 as a door closer circuit which will provide a steady 24 VDC
to door holders until an alarm or AC fail condition removes the power following a 10 second delay.
24
General Alarm
• HPF24S configured as Master (switch 3 OFF), NAC Outputs 1 through 4
Control Input #1; Sync Input is ignored.
• HPF24S configured as Slave (switch 3 ON), NAC Outputs 1 through 4
Control Input #1; Sync Input is monitored
• Resettable or nonresettable Auxiliary Power Output is available from TB4 Terminals 9 & 10.
Control Input #2 determines if reset will occur (must go from On to Off for a 6 second reset to
occur).
Split Alarm
• HPF24S configured as Master (switch 3 OFF), NAC Outputs 1 & 2 are controlled by Control
1
Input #1 and Outputs 3 & 4
• HPF24S configured as Slave
1
Input #1 and Outputs 3 & 4
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10
Split Temporal
• HPF24S configured as Master (switch 3 OFF), Control Input #1 controls NAC Outputs 1 & 2
and Control Input #2 controls Outputs 3 & 4
without sync; Sync Input is ignored.
• HPF24S configured as Slave (switch 3 ON), Control Input #1 controls NAC Outputs 1 & 2 and
Control Input #2 controls Outputs 3 & 4
sync; Sync Input is monitored for Outputs 1 & 2
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10
3
Selective Silence
• HPF24S configured as Master (switch 3 OFF), NAC Outputs 1 through 4
Control Input #1; Sync Input is ignored.
• Control Input #2 determines when Selective Silence for all outputs will occur.
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10
Table 3.3 Input/Output Configurations
Programmable Features Description
Input/Output Function
2
.
are controlled by Control Input #2; Sync Input is ignored.
4
(switch 3 ON), NAC Outputs 1 & 2 are controlled by Control
are controlled by Control Input #2; Sync Input is monitored
1
which will generate a Temporal code signal
1
which will generate a Temporal code signal without
2
.
HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
1
are controlled by
2
are controlled by
2
.
1
are controlled by