Dell 1000W User Manual page 48

Line-interactive rack ups 1000w, 1920/1500w, and 2700/2300w
Hide thumbs Also See for 1000W:
Table of Contents

Advertisement

Table 7. Settings (continued)
Description
Battery Saving Mode
On Battery Notice Delay
Site Wiring Fault Alarm
External Battery Module (EBM)
Charger
Battery Charge % to Restart
Battery Low Alarm
Automatic Battery Tests
48
|
Operation
Available Settings
[Disabled] [10%] [20%] [30%]...[100%]
The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.
[0] [1s] [2s]...[99s]
The UPS issues a "UPS on battery" notice in the
specified number of seconds after the UPS starts to
discharge the batteries.
[Enabled] [Disabled]
[0] [1]
See "Configuring the UPS for an EBM" on page 54.
[Enabled] [Disabled]
If Enabled, batteries charge normally.
If Disabled, the battery charger is off.
[0%] [10%] [20%] [30%]...[100%]
When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0, the feature is disabled.
[Immediate] [2 min] [3 min] [5 min]
If you select a value, the battery low alarm triggers
when the set amount of backup time
(approximately) remains in the batteries.
[Enabled] [Disabled]
See "Running Automatic Battery Tests" on page 55.
Default Setting
Disabled
0s
Disabled for 208V
models; Enabled for
all others
0
Enabled
0%
3 min
Enabled