18.3.7 To check for leaks after charging refrigerant
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
NOTICE
Any exposed piping can cause condensation.
7 Reattach the service cover and the piping intake plate.
8 Seal all gaps to prevent snow and small animals from entering the system.
a
a Seal
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
NOTICE
Do not block the air vents. This could affect air circulation inside the unit.
After charging refrigerant in the system an additional leak test must be performed.
Refer to
"19.8 To check refrigerant piping joints for leaks after charging
4
refrigerant" [
115].
18
Piping installation
|
Installer and user reference guide
107