Ratings - Slimfit Series 2 Boilers - Weil-McLain SlimFit 2 Series Manual

Commercial condensing gas-fired water boilers
Hide thumbs Also See for SlimFit 2 Series:
Table of Contents

Advertisement

SlimFit
Series 2
®
Ratings — SlimFit Series 2 boilers
Figure 107
Ratings and engineering data
Gross
Output
Input
Boiler
Model
MBH
MBH
Number
(Note 1)
(Note 1)
SF1000
1,000
958
SF1500
1,500
1,437
SF2000
2,000
1,906
Ratings shown are for sea level applications only. For altitudes above
1
sea level, the SlimFit boiler requires no modifications and automati-
cally de-rates itself by approximately 4% per 1,000 feet above sea
level. For elevations over 5,500 feet, see the high altitude section in
this manual for required control parameter changes.
The length of the vent and air piping will affect the maximum input.
See Figure 120, below for derate % vs vent/air piping length.
Net AHRI ratings are based on net installed radiation of sufficient
2
quantity for the requirements of the building and nothing need be
added for normal piping and pickup. Ratings are based on a piping
and pickup allowance of 1.15. An additional allowance should be
made for unusual piping and pickup loads.
Combustion efficiency is based on AHRI testing procedure
3
BTS-2000, and equal to 100% minus flue loss.
Figure 108
Derate due to vent/air piping length (graphs show maximum firing rate as % of rated input)
Determine vent/air piping equivalent length (feet) from Figure 24, page 29 — Use the length for
Derate % for Direct Exhaust
Boiler
6" vent piping
Derate % = 0.08 x L
SF1000
Example: If L=75 feet, Derate % = .08 x 75 = 6.0%
SF1500
NOT ALLOWED
SF2000
NOT ALLOWED
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
This document must only be used by a qualified heating installer/service technician. Read all instructions, including this addendum and the
Boiler Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death or substantial
property damage.
Installation must comply with local requirements and with the National Fuel Gas Code - ANSI Z223.1/NFPA54 – latest edition for U.S. instal-
lations or Natural Gas and Propane Installation Code - CAN/CSA B149.1 for Canadian installations.
116
commercial condensing gas
AHRI Ratings
Net
Combustion
Rating
Efficiency
Efficiency
MBH
%
(
(Note 2)
Note 3)
833
96.1
1,250
95.9
1,657
95.8
Notes
8" vent piping
NOT ALLOWED
Derate % = 0.03 x L
Example: If L=75 feet, Derate % = .03 x 75 = 2.3%
Derate % = 0.05 x L
Example: If L=95 feet, Derate % = .05 x 95 = 4.8%
— Boiler Manual
-
fired water boiler
Boiler
Thermal
Water
Vent/Air
Content
Pipe Size
%
Inches
Gallons
(Note 4)
(Note 5)
95.8
13
6, 8 or 10
95.8
19
8 or 10
95.3
25
8 or 10
Thermal efficiency is based on AHRI testing procedures BTS-2000.
4
SlimFit boilers can be direct vent or direct exhaust vented, either
5
through a side wall or through roof, as instructed in this manual and
compliant with all local codes. SlimFit Boilers require special venting,
consistent with Category IV boiler.
Category II, 10" venting requires 10" vent adapter, see pages 27-28
and Figure 96, page 105, "Vent/air piping components" for
adapter part numbers.
Use only the vent materials and methods identified in this manual.
The values are for the stack flow rate at the maximum firing rate for
6
the given boiler. The values can vary depending on the location of
the installation and operating conditions.
6" vent/air piping
Derate % = 3.0 + (0.08 x L)
Example: If L=60 feet, Derate % = 3.0 + .08 x 60 = 7.8%
NOT ALLOWED
NOT ALLOWED
Stack/vent
Boiler weight
flow rate
(pounds)
Dry
Operating
scfm
weight
weight
(no water)
(filled)
(Note 6)
279
865
975
418
1,050
1,210
558
1,250
1,460
Notes
L
in the equations
Derate % for Direct Vent
8" vent/air piping
Derate % = 0.04 x L
Example: If L=125 feet, Derate % = .04 x 125 = 5.0%
Derate % = 0.05 x L
Example: If L=80 feet, Derate % = .05 x 80 = 4.0%
Derate % = 0.07 x L
Example: If L=60 feet, Derate % = .07 x 60 = 4.2%
Part number 550-100-561/0224
Shipping
weight
1,130
1,310
1,510