Guidelines When Installing The Drain Piping - Daikin FXKQ20AMVEB Installation And Operation Manual

Vrv system air conditioner
Hide thumbs Also See for FXKQ20AMVEB:
Table of Contents

Advertisement

(accessory) can be used to prevent the washer for hanger bracket
(accessory) from falling during installation. Remove the clamp
washer for hanger bracket after the unit is mounted.
b
a
a
Clamp washer for hanger bracket (accessory)
b
Washer for hanger bracket (accessory)
Top view
a1
Top nut (field supply)
a2
Bottom double nut (field supply)
b
Washer for hanger bracket (accessory)
c
Hanger bracket (attached to the unit)
d
Decoration panel dimensions
e
Ceiling opening dimensions
f
Indoor unit dimensions
g
Suspension bolt pitch
Class
A (mm)
B (mm)
20~32
840
40~63
1240
Side view
a
b
a
Suspension bolt
b
Ceiling
NOTICE
Make sure the decoration panel overlaps the ceiling
opening by at least 20  mm. The distance between the
indoor unit and the ceiling opening must be ≤35 mm; if it is
more, install additional ceiling material or repair the ceiling.
a
b
≤35
≤35
d:
c:
≥20
490~510
a
Frame
b
Additional ceiling material
c
Ceiling opening
d
Ceiling overlapping part of the decorative panel
To mount the indoor unit
1 Handle the unit only by the hanger brackets.
FXKQ-A
VRV system air conditioner
3P747532-1A – 2023.11
a1
b
c
b
a2
f: A
g: B
e: C
d: D
(mm)
C (mm)
D (mm)
903
860~910
950
1303
1260~1310
1350
(mm)
d:
≥20
(mm)
2 Temporarily hang the unit on the 2 suspension bolts on one
side.
3 Insert the remaining 2 suspension bolts into the hanger bracket
and fix it securely with the bottom washer and nut.
4 Make sure that the unit is level.
a
a
Level
NOTICE
Do NOT install the unit tilted. Possible consequence: If
the unit is tilted against the direction of the condensate flow
(the drain piping side is raised), the float switch might
malfunction and cause water to drip.
12.2.2
Guidelines when installing the drain
piping
Make sure condensation water can be evacuated properly. This
involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
General guidelines
▪ Pipe length. Keep drain piping as short as possible.
▪ Pipe size. Keep the pipe size equal to or greater than that of the
connecting pipe (vinyl pipe of 25  mm nominal diameter and
32 mm outer diameter).
▪ Slope. Make sure the drain piping slopes down (at least 1/100) to
prevent air from being trapped in the piping. Use hanging bars as
shown.
1~1.5 m
a
a
Hanging bar
Allowed
12 Unit installation
Installation and operation manual
13