Fujitsu AIRSTAGE ASEH09KHCBN Service Manual page 81

Air conditioner wall mounted type
Table of Contents

Advertisement

2-16. E: 44. Human sensor error
Indicator
Indoor unit
Detective actuator
Indoor unit main PCB
Forecast of cause
Check point 1. Check the connector connection and cable open
Check if connector is loose or removed.
Check erroneous connection.
Check if sensor cable is open
Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Check the conduction or voltage
Conduction check (sensor connections error)
Disconnect the sensor and check the 2-3 pin on sensor connector.
→ith conduction: Sensor failure
→ithout conduction: Main PCB failure
Voltage check (sensor signal error)
Disconnect the sensor and check the voltage of 3 pin of the CN10 on the main PCB.
5 V: Sensor failure
Other than 5 V: Main PCB failure
2-16. E: 44. Human sensor error
Operation indicator
Timer indicator
Economy indicator
Error code
End
Continuous flash
1. Detect the open condition of the sensor.
2. →hen signal from sensor is "L" (0 V) for more than
20 min.
Connector connection failure
Main PCB failure
- (03-39) -
4 time flash
4 time flash
E: 44
Sensor failure