a19-1642
19XR TWO-STAGE COMPRESSOR ASSEMBLY TORQUES
Oil Heater Retaining Nut — ft-lb (N·m)
Bull Gear Retaining Bolt — ft-lb (N·m)
Demister Bolts — ft-lb (N·m)
Impeller Nut (Inner Locknut) — ft-lb (N·m)
Impeller Nut (Outer) — ft-lb (N·m)
Guide Vane Shaft Seal Nut/Bolts — ft-lb (N·m)
Fig. 57 — Compressor Assembly Torques — 19XR Two-Stage Compressors Frame Sizes 6 and 7
CAUTION
!
USE COPPER CONDUCTORS ONLY
UTILISEZ DES CONDUCTEURS EN CUIVRE SEULMENT
ALWAYS USE 2 WRENCHES TO TIGHTEN
• TERM INSULATOR TO MOTOR – 15-35 ft. lb.
• BRASS NUT TO TERM INSULATOR – 3 ft. lb. max
• ADAPTOR TO TERM STUD – 20-35 ft. lb.
• LUG BOLTS (1/2")– 32-45 ft. lb.
Insulate entire connection with electrical insulation
including 1 inch of cable insulation and 1 inch of the
term insulator.
1
TERMINAL STUD
2
3
ADAPTER
Mandatory for medium/high voltage.
MOTOR LEAD INSTALLATION LABEL
COMPRESSOR
INSULATION
TERMINAL
INSULATOR
BRASS NUT
13
FRAME 6
40-60 (54-81)
40-60 (54-81)
72-88 (98-119)
72-88 (98-119)
15-19 (20-26)
15-19 (20-26)
243-257 (329-348)
243-257 (329-348)
95-105 (129-142)
95-105 (129-142)
23-27 (31-37)
48-70 (64-94)