Specifications; Maintenance And Testing - Kidde Excellence Series Installation Sheet

Intelligent addressable single input module
Hide thumbs Also See for Excellence Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Table 7: Input status LED indications
State
Active 2
Active 1
Open circuit, short circuit
Test mode [1]
Active
Fault
Normal
Selected for test
Test activation
[1] These indications are only visible when the module is in Test mode.

Maintenance and testing

Maintenance and cleaning
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Clean the outside of the module using a damp cloth.
Testing
Test the module as described below.
See Figure 1 for the location of the Test (T) button, Device
Status LED, and Input status LED. See Table 6 and Table 7 for
status LED indications.
To perform the test:
1.
Press and hold the Test (T) button for at least 3 seconds
(long press) until the Device status LED flashes red (fast
flashing), and then release the button.
The module enters Test mode.
The Device status LED flashes red for the duration of the
test.
The Input status LED indicates the input state on entering
Test mode: normal (steady green), active (steady red), or
fault (steady yellow).
Note:
The input can only be tested when the input state is
normal. If the LED indicates an active or fault state, exit
the test.
2.
Press the Test (T) button again (short press) to start the
test.
The Input status LED flashes red (slow flashing) to
indicate the test.
The input activates for 30 seconds and the activation
status is sent to the control panel.
Press the Test (T) button again to extend the input
activation test for another 30 seconds, if required.
3.
To stop the test and exit Test mode, press and hold the
Test (T) button again for at least 3 seconds (long press).
The module exits the test automatically after 5 minutes if
the Test (T) button is not pressed.
After the test the input returns to its original state.
Note:
If the input is activated, the Input status LED indicates
the activation state when the module exits Test mode. Reset
the control panel to clear the LED indication.
P/N 12-0201-501-4000-01 • ISS 21NOV23
Indication
Steady red LED
Flashing red LED
Flashing yellow LED
Steady red LED
Steady yellow LED
Steady green LED
Flashing green LED
Flashing red LED

Specifications

Electrical
Operating voltage
Current consumption
Standby
Active
End-of-line resistor
Polarity sensitive
Number of inputs
Isolation
Current consumption (isolation
active)
Isolation voltage
Minimum
Maximum
Reconnect voltage
Minimum
Maximum
Rated current
Continuous (switch closed)
Switching (short circuit)
Leakage current
Series impedance
Maximum impedance [1]
Between the first isolator and
the control panel
Between each isolator
Number of isolators per loop
Number of devices between
isolators
[1] Equivalent to 500 m of 1.5 mm
Mechanical and environmental
IP rating
Operating environment
Operating temperature
Storage temperature
Relative humidity
Colour
Material
Weight
Dimensions (W × H × D)
Protective housing
Install the module inside protective housing that meets the
following specifications.
IP rating
Material
Weight [1]
[1] Excluding the module.
17 to 29 VDC (4 to 11 V pulsed)
250 µA A at 24 VDC
2.5 mA at 24 VDC
15 kΩ, ¼ W, 1%
Yes
1
2.5 mA
14 VDC
15.5 VDC
14 VDC
15.5 VDC
1.05 A
1.4 A
1 mA max.
0.08 Ω max.
13 Ω
13 Ω
128 max.
32 max.
2
(16 AWG) cable.
IP30
−22 to +55°C
−30 to +65°C
10 to 93% (noncondensing)
White (similar to RAL 9003)
ABS+PC
60 g
87 × 80 × 26 mm
Min. IP30 (indoor installation)
Metal
Min. 4.75 kg
3 / 31