RANGER 305D
FIGURE .2 CONNECTION OF R NGER 305D TO PREMISES WIRING
POWER
240 Volt
60 Hz.
COMPANY
3-Wire
Service
METER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE
W RNING
Only a licensed, certified, trained electrician should install
the machine to a premises or residential electrical system.
Be certain that:
• The installation complies with the National Electrical Code
and all other applicable electrical codes.
• The premises is isolated and no feedback into the utility
system can occur. Certain state and local laws require
the premises to be isolated before the generator is
linked to the premises. Check your state and local
requirements.
• A double pole, double throw transfer switch in conjunction
with the properly rated double-pole/ double throw
circuit breaker is connected between the generator
power and the utility meter.
240 VOLT
120 VOLT
120 VOLT
50AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
240 VOLT
BREAKER
GND
A 12
GROUNDED CONDUCTOR
NEUTRAL
BUS
GROUND
N
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
INSTALLATION
N
LOAD
PREMISES
DISCONNECT AND
SERVICE
OVERCURRENT
PROTECTION