Toshiba MMY-MAP0806FT8P-E Installation Manual page 21

Air conditioner (multi type)
Hide thumbs Also See for MMY-MAP0806FT8P-E:
Table of Contents

Advertisement

Group control through a Remote Controller
Group control of multiple indoor units (8 units) through one or two remote controller switch.
Indoor unit
No.1
No.2
No.3
A B
A B
A B
(A.B)
Remote controller
For the group connection within each branch of the Multi port type FS unit and Single port type FS unit
(Long piping model) :
It is up to 8 units if one remote controller is used, and it is up to 7 units if two remote controllers are used.
Connection of power wires and communication wires
Remove knockouts on the piping/wiring panel on the front of the unit and the panel on the bottom to get the power
and communication wires through the holes.
Knockout for the
communication wire
Knockout for the power
wire
NOTE
Be sure to separate the power wire and communication wires.
39-EN
No.4
No.7
No.8
A B
A B
A B
Piping/wiring panel
Knockout for the power
supply wire
Earth screw
Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the electrical control box and connect the power
supply wire to the power supply terminal block and the earth line to the earth screw. After that, x the power
supply wire with the 2 cord clamps.
2. Be sure to use round-type crimping terminals for power connection.
Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to x the terminal screws.
10 mm or more
Attached clamp lter
Fixed on attached binding band
(only MAP160 to MAP200 type)
– 20 –
Power supply terminal block
Clamp lter
(only MAP160 to MAP200 type)
Cord clamps
Communication terminal block
Power supply wires
Cord clamp
Communication wires
L
L
L
N
1
2
3
L1
L2
L3
N
Power supply wire
Earth line
EN
ID
ID
40-EN

Advertisement

Table of Contents
loading