3.1 Wiring Precautions
r: Internal resistor of limit switch (kΩ)
R: Bleeder resistor (kΩ)
The input off voltage is 2.5 V. Therefore, when the power supply voltage is 2.4 V,
the input impedance is 3.6kΩ.
2.4-2.5
I ×
or more
r
Obtain R so that the above current will flow. Obtain I in the same way as when using the above
2-wire sensor.
9
R≤
(kΩ) W=
3.6I-2.5
3.1.3 Precautions on Output Wiring
■
Connection of inductive loads
When connecting an inductive load, a protective circuit should be installed in parallel with the
load.
When connecting the DC type inductive loads and relay type output unit, be sure to connect a
diode for protective circuit across the ends of the load. This will affect the life of the relay.
When using an AC inductive load (Relay output type)
■
Connection of capacitive loads
When connecting the loads with large in-rush currents, be sure to connect a protection circuit in
series with the load.
3-4
2
(Power supply voltage)
R
×(3 to 5)
WUME-FP7DIO-05