Terminal layout
Although the positive and negative terminals are connected internally, connect these terminals
externally as well.
2.3.6 64-point Sink-type Transistor Output Unit
■
Description
Items
Insulation system
Output type
Rated load voltage
Allowable load voltage range
Max. load current
Common limits
Max. inrush current
OFF state leakage current
ON state max. voltage drop
Response time
External power
supply
WUME-FP7DIO-05
0.3 A specifications
(Y0 to 7)
0.1 A specifications
(other than the above)
OFF→ON
ON→OFF
Voltage
AFP7Y64T
Optical coupler
Open collector
5 to 24 V DC
4.75 to 26.4 V DC
0.3 A (20.4 to 26.4 V DC) and 30 mA (4.75 V DC)
0.1 A (20.4 to 26.4 V DC) and 15 mA (4.75 V DC)
3.2 A/common
0.6A
1 μA or less
0.5 V or less
0.1 ms or less (Load current: 2 mA or more)
0.3 ms or less (Load current: 2 mA or more)
4.75 to 26.4 V DC
2.3 Output Unit Specifications