 Settings for each type (TA, TF, DDC)
Set with the SW501 switch on the control P.C. board MCC-1777.
TA type: Set all SW501 to OFF.
Turn off Bit3 of SW501.
ON
SW501
OFF
TF type: Turn on only Bit2 of SW501.
Turn off Bit3 of SW501.
ON
SW501
OFF
DDC type (0 - 10 V) Stepped Control: Turn on only Bit3 of SW501. (Refer to AI3 / AI3 for details)
ON
SW501
OFF
DDC type (0 - 10 V) Linear Control: Turn on Bit3 and Bit4 of SW501. (Refer to AI3 / AI3 for details)
ON
SW501
OFF
LED position and details
D505
D504 D503
LED
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
D501
P.C. board LED
D501 MCU power supply
D503 Main bus communication
D504 Sub bus communication
D505 Mod bus communication When connected to Modbus, it lights up every 5 seconds.
D403 Sub bus power supply
D403
LED
Meaning of lighting
Lights when the power is turned on
Flashes every 5 seconds.
With central control: lighting and flashing every 5 seconds.
Flashes every 5 seconds.
Group: lighting and flashing every 5 seconds.
Sub bus lights while power is being supplied.