Toshiba TCB-DP22CUL Installation Manual

Drain pump kit
Hide thumbs Also See for TCB-DP22CUL:

Advertisement

AIR CONDITIONER

Installation Manual

Drain Pump Kit
Model name :
TCB-DP22CUL
(SPLIT TYPE)
Installation Manual
Air Conditioner (Split type)
Manuel D'installation
Climatiseur (Type split)
2
English
12
Français

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba TCB-DP22CUL

  • Page 1: Installation Manual

    AIR CONDITIONER (SPLIT TYPE) Installation Manual Drain Pump Kit Model name : TCB-DP22CUL Installation Manual English Air Conditioner (Split type) Manuel D’installation Français Climatiseur (Type split)
  • Page 2: Table Of Contents

    Drain Pump Kit Installation Manual Please read this Installation Manual carefully before installing the Air Conditioner. • This Manual describes the installation method of the DRAIN PUMP KIT. • For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit. WARNING For this Drain Pump Kit, please use the Elbow Piping Kit (MODEL: TCB-KP12CUL, TCB-KP22CUL) sold separately.
  • Page 3: Accessory Parts And Parts To Be Procured Locally

    For fixing Drain Pump Kit Screw For fixing fixture of Drain Pump Kit Banding band For fixing wires r Specification Drain Pump Kit model name Height of drain up TCB-DP22CUL 23.6” (600mm) or lower from top face of the set English-2...
  • Page 4: Precautions For Safety

    Drain Pump Kit Installation Manual PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. •...
  • Page 5: Preparation For Installation Of Drain Pump Kit

    Drain Pump Kit Installation Manual PREPARATION FOR INSTALLATION OF DRAIN PUMP KIT n Cautions on installation • In the installation work of the Drain Pump Kit, the pipe cannot be drawn out from other side than the upper side. • Apply thermal insulation for all the drain pipes. •...
  • Page 6: Installation Procedure Of Drain Pump Kit

    Drain Pump Kit Installation Manual INSTALLATION PROCEDURE OF DRAIN PUMP KIT n Before installation 1. Removal of suction grille NOTE Slide the suction grille fixing knobs After installation of the Drain Pump Kit, be sure to (2 positions) toward the arrow direction, and mount the wire guard as original.
  • Page 7: Tightening Connection

    Drain Pump Kit Installation Manual n Knockout hole u Tightening connection Open the draw-out port (Knockout hole) at upper CAUTION side. • Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions. Draw-out port at upper side Unit : ft lbs (N•m) (Knockout hole) Outer diam.
  • Page 8 Drain Pump Kit Installation Manual n Thermal insulating process n How to install Drain Pump Kit Apply thermal insulation to pipes at liquid and gas 1. Mount the Drain Pump Kit fixture to the rear sides separately. side inside of the indoor unit. (1 screw) •...
  • Page 9 Drain Pump Kit Installation Manual n Connection of drain hose at n Connection of drain hose at indoor unit side Drain Pump Kit side 1. Insert the drain hose attached to the indoor unit 1. Insert the drain hose attached to the Drain Pump into the drain pipe connecting port of the indoor Kit into the connecting port of drain pipes at the unit’s and into the drain pipe connecting port of...
  • Page 10: Drain Piping Work

    Drain Pump Kit Installation Manual DRAIN PIPING WORK n Piping/Heat insulating material CAUTION Require the following materials for piping and heat insulating at site. • Following the Installation Manual, perform the drain piping work so that water is properly drained, Hard vinyl chloride pipe VP25 and apply a heat insulation so as not to cause a dew.
  • Page 11: Cable Connection

    Drain Pump Kit Installation Manual CABLE CONNECTION 1. Loosen the mounting screws (2 positions) of the cover of the electric parts box, and then remove the cover. 2. In the Drain Pump Kit, connect the connector (Blue 3P) for drain pump to P.C. board CN68 (Blue 3P) of the indoor unit, and the connector (Red 3P) for float switch to P.C.
  • Page 12 EH99866301...

Table of Contents