Download Print this page

LG Therma V FHNW16606C0 Data Book page 51

Advertisement

Installation of Outdoor Unit
2. Selection of the best Location
2.3 Lifting method
Corner
< ! > CAUTION
• Be very careful while carrying the product.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
• Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it.
Otherwise plastic packaging bag may suffocate children to death.
• When carrying in Outdoor Unit, be sure to support it at four points.
Carrying in and lifting with 3-point support may make Outdoor Unit unstable, resulting in a fall.
• Use 2 belts of at least 8m(26.2ft) long.
• Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
Sub line
40º or less
A
Intake hole
Air outlet grille
Always hold the unit by the corners, as holding
it by the side intake holes on the casing may
cause them to deform.
Forklift
Put the sling belt (delivered as accessory) through
the unit's foot.
Carry the unit using the sling belts and the unit's han-
dle (right), and put it onto the installation structure.
Remove the sling belts and dispose them.
4
Installation