1. Specifications
Technical specifications
Type
Model (maker, name)
Motor type
Water pump***
Steps of pumping performance
Power input
Max. head
Type
Model (maker, name)
Motor type
Water pump 2***
Steps of pumping performance
Power input
Max. head
Type
Heat exchanger
No.
Number of plate
(refrigerant to water)
Water volume
Supply type
Mesh size
Water strainer
Max. particle size
Material
Safety valve
Pressure limit
(water cycle)
Type
Model(maker,name)
Flow sensor
Measuring
range
Trigger point
Model (maker, name)
Measuring
Water pressure sensor
range
Sound pressure level
Heating(rated, @5m)
Sound power level
Heating
Water connecting
Inlet
Outlet
pipes
Net(W x H x D)
Dimensions
Shipping(W x H x D)
Net
Weight
Shipping
Color of front grille
Exterior
RAL Code of front grille
Note
1. Due to our policy of innovation, some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And "Electric characteristics" chapter should be considered for
electrical work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound power level is measured in accordance with EN 12102-1 and ISO 9614.
• Rated : This mode is measured on the rated condition in the semi-anechoic rooms. Therefore, these values may vary depending on operation
conditions.
• Daytime max : This mode is measured based on max. fan RPM and max. compressor Hz. that can be reached under outdoor air temperature 2°C.
• Low noise : This mode lowers noise by limiting the compressor Hz. and fan RPM, and thus the performance may be limited.
4. Performances are accordance with EN14511 and reflect ErP testing conditions. The values indicated above are the declared values at rated
conditions acc. ErP regulation. For max. capacities, please refer to Performance Data.
5. This product contains Fluorinated greenhouse gases.
6. SCOP is in accordance with EN14825.
7. Rated running currents are based on the declared values under the following conditions.
• Heating : Outdoor Temp. 7°CDB / 6°CWB, Leaving Water Temp. 35℃
• Cooling : Outdoor Temp. 35°C(DB) / 24°C(WB), Leaving Water Temp. 18°C
8. All installation sites must be equipped with an earth leakage circuit breaker (ELCB).
* DHW 65~80°C Operating is available only when the booster heater is operating.
** This is the power input i accordance with the 80% pump capacity setting at rated water flow rate. When the OH SUNG pump is set as 80%
capacity, it's head is similar to that of the GRUNDFOS pump at rated water flow rate.
In the case of integrated water pump, either water pump or water pump 2 will be applied.
***
-
-
-
-
Min.~Max.
W
Rated
W
m
-
-
-
-
Min.~Max.
W
Rated
W
m
-
-
EA
-
mesh
mm
-
Upper limit
bar
-
-
Min. ~ Max.
ℓ /min
ℓ /min
-
Min. ~ Max.
bar
dB(A)
Low noise
dB(A)
Rated
dB(A)
Daytime max.
dB(A)
inch
inch
mm
mm
kg
kg
-
-
FHBW166B0
[HM161HF UB60]
Canned type for hot water circulation
GRUNDFOS, UPML GEO 20-105 CHBL
BLDC
Variable speed 10% to 100%
17~152
145
11
Canned type for hot water circulation
OH SUNG, ODM-061P
BLDC
Variable speed 10% to 100%
17 ~ 152
145
11
Brazed plate HEX
1
76
1
Loose supply (externally installed)
30
0.6
Stainless steel
3.0
Vortex
SIKA VVXC9SNBUC00252P
5 ~ 80
10
Sensata OFM(2HMP)
0 ~ 20
30
51
52
61
Male PT 1" according to ISO 7-1 (tapered pipe threads)
Male PT 1" according to ISO 7-1 (tapered pipe threads)
1,560 x 1,019 x 520
1,620 x 1,180 x 625
181.0
199.0
Dark dawn gray
RAL 7012