Viessmann Vitomax LW Operating And Service Instructions page 28

Low pressure hot water boilers
Hide thumbs Also See for Vitomax LW:
Table of Contents

Advertisement

Operating conditions
Operating conditions
1.
Heating water flow rate
2.
Boiler return temperature
(minimum value)
Gas operation:
Oil operation:
3.
Minimum flow temperature
4.
Max. temperature spread
Gas operation:
Oil operation:
5.
Stepped burner operation
6.
Modulating burner operation
7.
Reduced mode
Single boiler system
Multi boiler system
Lead boiler
Lag boiler
Weekend setback
Tab. 13
Note
Boiler types M82 and M84 can also be operated with
fuel oil S (heavy fuel oil).
Boiler type M64 can be operated with fuel oil S follow-
ing conversion (option incurs additional charge).
Note
For combustion of heavy fuel oil to DIN 51603-5, the
average boiler water temperature must be at least
90 °C.
28
All manuals and user guides at all-guides.com
Vitomax
M148
LW with
Vitotrans
100-LW/
200-LW
No minimum heating water flow rate required
65 °C
65 °C
70 °C
40 K
40 K
Operation with minimum flow temperature
Operation with minimum flow temperature
Lag boilers can be shut down
M62C
M64B
Requirements/notes
55 °C
50 °C
70 °C
50 K
50 K
None
None
See reduced mode
Boiler datasheet
See chapter "Standard values for water quality"
on page 11