Oxygen Sensor Qgo20 - Riello RS 68/EV O2 ULX Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

3.15 Oxygen sensor QGO20 ... (optional)
Warnings
To avoid accidents, material or environmen-
tal damage, observe the following instruc-
tions!
WARNING
Avoid opening, modifying or forcing the oxy-
gen sensor.
 All interventions (assembly and installation operations,
assistance, etc.) must be carried out by qualified personnel.
 Before modifying the wiring in the sensor connection area,
fully disconnect the burner control device from the power
supply (omnipolar separation).
 Ensure that the sensor cannot be inadvertently switched on
again and check this by making a voltage test.
 To avoid the risk of electrocution, protect the connection ter-
minals in a suitable manner and correctly fix the cover.
 During operation, the flange of the sensor connection must
be kept closed; all screws must be tightened securely.
 Check the wiring is in order.
 Falls and collisions can negatively affect the safety func-
tions. In this case, the unit must not be operated, even if it
displays no evident damage.
 Ensure that the device does not get into contact with explo-
sive or inflammable gases.
 There is a risk of burning since the measuring cell works at
an operating temperature of 700 °C and other accessible
parts can get very hot too (> 60 °C).
 To prevent injury caused by the hot immersion tube, remove
the device only after the equipment has cooled down.
 Make certain that the sensor's inlet and outlet are always
kept free from dirt.
 Before cleaning the inlet and outlet, allow the sensor to cool
down for at least 1 hour.
 Mount the sensor such that the connecting part (head to
flange) is free so that the exchange of air is ensured. Other-
wise, measurements might get distorted, possibly leading to
dangerous situations.
 Ensure that there are no chemicals, such as solvent vapors,
near the sensor.
Installation notes
 The flue gas flow passing the measuring cell must be homo-
geneous, with no or only little turbulence. When mounted too
close to air dampers or pipe bends, faulty measurements
can occur.
 A number of faults can distort the measurements (this can
lead to dangerous situations in connection with oxygen trim
control):
– If the stack is not tight, false air can join the flue gases.
– In that case, the residual oxygen content indicated by the
sensor is higher than it actually is.
– If the flue gas velocity is low, the sensor's response is
slower, since the flue gases take more time to pass the
measuring cell. In that case, it is recommended to mount
the sensor in an inclined position (refer to the manual).
– The greater the sensor's distance from the flame, the lon-
ger the dead time.
20205796
Technical description of the burner
NOTE:
For further explanations about the wiring connetions, please
refer to the manual supplied with the accessory code
20045187.
18
GB
Condensation, formation of ice and the entrance
of water are not permitted!
WARNING
S9895
Fig. 12

Advertisement

Table of Contents
loading

Table of Contents