Pll52; Terminal Ratings, Cable Lengths And Cross-Sectional Areas - Riello RS 68/EV O2 ULX Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

3.14 PLL52... module (optional)
Warnings
To avoid accidents, material or environmen-
tal damage, observe the following instruc-
tions!
WARNING
Avoid opening, modifying or forcing the de-
vice.
 All interventions (assembly and installation operations,
assistance, etc.) must be carried out by qualified personnel.
 Falls and collisions can negatively affect the safety func-
tions. In this case, the unit must not be operated, even if it
displays no evident damage.
Assembly notes
Check the relevant national safety standards are respected.
3.14.1 Terminal ratings, cable lengths and cross-
sectional areas
Cable lengths / cross-sectional areas
Electrical connection "X89"
Cable lengths
Cross-sectional areas
Analog inputs
Air temperature detector
Flue gas temperature
QGO20...
Interface
Technical description of the burner
Screw terminals up to max. 2.5
2
mm
10 m fino a QGO20...
Refer to description of QGO20...
Pt1000 / LG-Ni1000
Pt1000 / LG-Ni1000
Refer to data sheet N7842
Communication bus for LMV52...
Tab. J
S9902
Technical data
Model
Mains voltage "X89-01"
Safety class
Mains frequency
Power consumption
Degree protection
Transformer AGG5.220
- Primary side
- Secondary side
Environmental conditions:
Storage
Climatic conditions:
Mechanical conditions:
Temperature range:
Humidity:
Transport
Climatic conditions:
Mechanical conditions:
Temperature range:
Humidity:
Operation
Climatic conditions:
Mechanical conditions:
Temperature range:
Humidity:
NOTE:
For detailed information, refer to the specific manual of
PLL52 module.
Condensation, formation of ice and the entrance
of water are not permitted!
WARNING
17
GB

PLL52...

AC 230 V -15%/10%
I class with parts according to II
class (DIN EN 60730-1)
50 / 60 Hz ±6 %
Ca. 4 VA
IP54, housing closed
AC 230V
AC 12 V (3x)
DIN EN 60721-3-1
Class 1K3
Class 1M2
-20...+60 °C
<95% r.h.
DIN EN 60721-3-2
Class 2K2
Class 2M2
-25...+70 °C
<95% r.h.
DIN EN 60 721-3-1
Class 3K5
Class 3M2
-20...+60 °C
< 95% r.h.
Fig. 11
Tab. K
20205796

Advertisement