Bryant 559K 08 Series Service And Maintenance Instructions page 51

Single package rooftop electric cooling unit with puron (r-410a) refrigerant 7.5 to 15 nominal tons
Table of Contents

Advertisement

MENU
PARAMETER
VENTMIN L
VENTMIN M
VENTMIN H
EXH1 SET
EXH1 L SET
SETPOINTS
(CONT)
EXH1 M SET
EXH1 H SET
EXH2 L SET
EXH2 M SET
EXH2 H SET
INSTALL
UNITS DEG
EQUIPMENT
AUX2 IN
FAN SPEED
SYSTEM
SETUP
FAN CFM
AUX1 OUT
OCC
FACTORY
DEFAULT
Table 12 — W7220 Menu Structure
PARAMETER
PARAMETER
DEFAULT
RANGE AND
VALUE
INCREMENT
f
3.7 V
2 to 10 vdc
3.4 V
2 to 10 vdc
2.8 V
2 to 10 vdc
50%
0 to 100%
65%
0 to 100%
60%
0 to 100%
50%
0 to 100%
80%
0 to 100%
77%
0 to 100%
75%
0 to 100%
01/01/17
N/A
°F
°F or °C
Conventional or
CONV
HP
SD/W or
W
HP(O)/HP(B)
1 speed
2 speed
2 speed
2SP H/C
3 speed
100 to 15000
cfm;
5000cfm
increment by
100
NONE
NONE
EXH2
SYS
INPUT or
INPUT
ALWAYS
NO
NO or YES
a,b,c,d,e
EXPANDED PARAMETER NAME
DCV MINIMUM DAMPER POSITION AT LOW SPEED. Only displays if unit
is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2 speed with 1
heat and 1 cool then set for HEATING ventilation. If using 3 speed with 1
heat and 2 cool then set for LOW SPEED COOLING
DCV MINIMUM DAMPER POSITION AT MEDIUM SPEED. Only displays if
unit is set for 3 speed with 1 heat and 2 cool. Set for HEATING ventilation.
DCV MINIMUM DAMPER POSITION AT HIGH SPEED. Only displays if
unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2 speed
with 1 heat and 1 cool then set for COOLING ventilation. If using 3 speed
with 1 heat and 2 cool then set for HIGH SPEED COOLING ventilation
Exhaust fan set point for single speed units. Based on OA Damper position
to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT LOW SPEED on 2 speed or 3 speed with
1 heat and 2 cool. Based on economizer OA damper position to activate
power exhaust.
EXHAUST POINT 1 SETPOINT AT MEDIUM SPEED. Only displays if unit
is set for 3 speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT HIGH SPEED on 2 speed or 3 speed with
1 heat and 2 cool. Based on economizer OA damper position to activate
power exhaust.
EXHAUST FAN 2 SETPOINT AT LOW SPEED on 2 speed or 3 speed with
1 heat and 2 cool. Based on economizer OA damper position to activate
power exhaust.
EXHAUST FAN 2 SETPOINT AT MEDIUM SPEED. Only displays if unit is
set for 3 speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT HIGH SPEED on 2 speed or 3 speed with
1 heat and 2 cool. Based on economizer OA damper position to activate
power exhaust.
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
Sets economizer controller in degrees Fahrenheit or Celsius
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump input from
thermostat or controller. See Menu Note e.
In CONV mode:
SD + Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode for W.
Shutdown is not available in 2-speed fan mode. See Menu Note e.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
Sets the economizer controller operation based on 1 speed, 2 speed,
2 speed heat/cool (2SP H/C), or 3 speed supply fan.
NOTE: Multi-speed fan options also need Heat (W1) programmed in AUX 2
In. See Menu Note e.
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate label for the specific unit.
Select OUTPUT for AUX1 O relay
NONE = not configured (output is not used)
EXH2 = second damper position relay closure for second exhaust fan
SYS = use output as an alarm signal
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac), the 24 vac is
input "INPUT" to the OCC terminal. If no occupancy output from the
thermostat then change program to "ALWAYS" OR add a jumper from
terminal R to OCC terminal.
Resets all set points to factory defaults when set to YES. LCD will briefly
flash YES and change to NO but all parameters will change to the factory
default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed values.