Bryant 559K 08 Series Service And Maintenance Instructions page 46

Single package rooftop electric cooling unit with puron (r-410a) refrigerant 7.5 to 15 nominal tons
Table of Contents

Advertisement

OUTPUTS
Actuator Signal
2-10 vdc; minimum actuator impedance is 2k ohm; bus two-wire
output for bus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O
All Relay Outputs (at 30 vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
ENVIRONMENTAL
Operating Temperature
–40 to 150°F (–40 to 65°C).
Exception of display operation down to –4°F (–20°C) with full
recovery at –4°F (–20°C) from exposure to –40°F (–40°C).
Fig. 69 — Typical EconoMi$er X (W7220 Controller) Wiring
Storage Temperature
–40 to 150°F (–40 to 65°C)
Shipping Temperature
–40 to 150°F (–40 to 65°C)
Relative Humidity
5% to 95% RH non-condensing
ECONOMIZER MODULE WIRING DETAILS
Use Fig. 70 and Tables 8 and 9 to locate the wiring terminals for
the economizer module.
NOTE: The four terminal blocks are removable. Slide out each
terminal block, wire it, and then slide it back into place.
46