Bryant 559K 08 Series Service And Maintenance Instructions page 47

Single package rooftop electric cooling unit with puron (r-410a) refrigerant 7.5 to 15 nominal tons
Table of Contents

Advertisement

MAT
MA
MAT
MA
OAT
OA
OAT
OA
S-BUS
SB
SB
S-BUS
SB
SB
SB
SB
V
IAQ 2-10
C
R
IAQCOM
IAQ 24V
V
C
ACT 2-10
R
NA
ACT COM
ACT 24V
50040839-001
Rev. G
Fig. 70 — W7220 Wiring Terminals
Table 8 — Economizer Module- Left Hand Terminal
LABEL
TYPE
Top Left Terminal Block
MAT
20k NTC and
Mixed Air Temperature Sensor (Polarity
MAT
COM
Insensitive Connection)
OAT
20k NTC and
Outdoor Air Temperature Sensor
OAT
COM
(Polarity Insensitive Connection)
S-BUS
S-BUS
Enthalpy Control Sensor
S-BUS
(Sylk™
a
Bus)
(Polarity Insensitive Connection)
Bottom Left Terminal Block
Air Quality Sensor Input (e.g., CO
IAQ 2-10
2-10 vdc
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 vac
Air Quality Sensor 24 vac Source
ACT 2-10
2-10 vdc
Damper Actuator Output (2-10 vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24v
24 vac
Damper Actuator 24 vac Source
NOTE(S):
a. Third-party trademarks and logos are the property of their respective
owners.
NA
AUX2-
NA
A2
OCC
OCC
E-GND
EXH1
EX
A1
AUX1-O
Certified FDD Product
California Title 24, Part 6
HJW10
www.energy.ca.gov
Y2-
Y2I
Y2O
Y2-O
Y1I
Y1-
Y1O
Y1-O
C
R
50048848-002
Rev. A
Blocks
DESCRIPTION
Table 9 — Economizer Module-Right Hand Terminal
LABEL
AUX2 I
24 vac IN
OCC
24 vac IN
E-GND
E-GND
EXH1
24 vac OUT Exhaust Fan 1 Output
AUX1 O
24 vac OUT
Y2-I
24 vac IN
Y2-O
24 vac OUT
Y1-I
24 vac IN
Y1-O
24 vac OUT
C
COM
R
24 vac
C
S-BUS SENSOR WIRING
R
The labels on the sensors and controller are color coded for ease of
installation. Orange labeled sensors can only be wired to orange
terminals on the controller. Brown labeled sensors can only be
wired to S-bus (brown) terminals. Use Fig. 71 and Table 10 to lo-
cate the wiring terminals for each S-Bus sensor.
Use Fig. 71 and Table 10 to locate the wiring terminals for each
enthalpy control sensor.
2
S-BUS
Terminals
(1 and 2)
Fig. 71 — S-Bus Sensor DIP Switches
47
Blocks
TYPE
DESCRIPTION
Top Right Terminal Blocks
The first terminal is not used.
Shut Down (SD) or HEAT (W)
Conventional only
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
Occupied/Unoccupied Input
Programmable:
Exhaust fan 2 output
or
System alarm output
Bottom Right Terminal Blocks
Y2 in - Cooling Stage 2 Input from space
thermostat
Y2 out - Cooling Stage 2 Output to stage
2 mechanical cooling
Y1 in - Cooling Stage 2 Input from space
thermostat
Y1 out - Cooling Stage 2 Output to stage
2 mechanical cooling
24 vac Common
24 vac Power (hot)
DIP
Switch
Label
DIP
Switches
(3)
S-BUS
2 Pin Side
Connector