2 Simple Application Controllers
13.4.7

Applicable Error Checks

In the event that the input voltage is greater than 11 V or equal to 0V the following system flags
will be set.
Table 13.8:
M17
M18
M19
M20
M21
M22
M23
M24
- If the flags in the table above are activated, check that:
• a sensor is connected
• there is not a break in the sensor connection
• the temperature is not greater than the specified limit
• power is being supplied to the AL2-2TC-ADP.
- If the "Error" message appears instead of "OK" while offset/gain calibration, check that:
• The power is being supplied to the AL2-2TC-ADP.
• The AL2-2TC-ADP is connected to α2 correctly.
• The input, which connects the AL2-2TC-ADP is selected for calibration.
• The AL2-2TC-ADP inputs are left unconnected.
• The jumpers on AL2-2TC-ADP is either placed on the "-50°C" position or the "450°C"
position.
• The calibration menu entry related to the jumper position is selected ("-50°C" or "450°C").