Follett 25CI425A Installation, Operation And Service Manual page 27

Ice and water dispensers
Table of Contents

Advertisement

Loss of water
During operation, the water level cycles between the normal low (D) and normal high (C) water probes - the fill
valve (P21) cycling on and off. If continuity is not detected between the common probe (B) and normal low (D)
within 10 seconds, the LOW WATER and TIME DELAY LEDs will come on and the machine will shut down for
the one hour time delay period. After the time delay, the fill valve will re-energize and wait for continuity between
the common probe and normal high before restarting. LOW WATER LED will remain ON until the water level is
satisfied.