Fx 2N -4Da - Mitsubishi Electric MELSEC-FX3S Series Manual

Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
Common Items
4.2.4
FX
-4DA
2N
Specifications
Number of output points
Analog output range
Offset
Gain
Digital output
Resolution
Overall accuracy
Time required for D/A
conversion
Output characteristics
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method
• The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1.
Adjustment of the offset or gain value will not affect the resolution.
*2.
The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset) ≤ 15V
*3.
The offset and the gain should satisfy the following condition:
4mA ≤ (Gain - Offset) ≤ 32mA
A-38
PLC User's Manual - Analog Control Edition
3UC
Voltage output
-10V to +10V DC
(External load: 2 k to 1 MΩ)
-5V to +5V
15 V or less, and
Gain - Offset ≥ 1V
With sign, 12 bits, binary
5mV (10V × 1/2000)
±1.0% (±200mV) for 20V full scale
Does not include any load fluctuation.
2.1 ms (The number of selected channels will not affect this value.)
 When the output mode is set to "0":
+10V
-2000
0
+2000
-10V
FX
- 4DA
2N
4ch
*1*2
*1
4 Comparison of Performance Specifications
Current output
0mA to 20mA DC
4mA to 20mA DC
(External load: 500 Ω or less)
-20mA to +20mA
32 mA or less, and
Gain - Offset ≥ 4mA
10 bits, binary
20μA (20mA × 1/1000)
±1.0% (±200μA) for 20mA full scale
Same accuracy for 4mA to 20mA output
-
When the output mode is "2":
(The dotted line is for mode 1.)
20mA
4mA
0
1000
Digital input
4.2 Analog Output
*1*3
*1