This chapter describes the minimum programming necessary for analog output by the FX
Follow the procedure below to confirm that correct analog values can be output.
4.1

Analog Output Procedures

1
Unit number check
Unit numbers from 0 to 7 will be assigned to the special function units/blocks starting from the left.
When the units/blocks are connected to the FX
are assigned. Check the unit number assigned to the FX
Main unit
(FX
Series
3U
PLC)
2
Output mode (BFM#0) setting
Depending on the analog signal generator to be connected, set the output mode (BFM#0) for each
channel.
Use hexadecimal numbers for output mode setting. Set the corresponding channel digit to the
output mode setting value specified in the following table:
Setting
value
0
Voltage output mode
Voltage output
1
analog value mV specification mode
2
Current output mode
3
Current output mode
Current output
4
analog value μA specification mode
F
Channel not used
→ For a detailed description of the standard output characteristics, refer to Section 2.4.
PLC User's Manual - Analog Control Edition
Unit
number: 0
Input/output
Special
extension
function block
block
H
ch4
ch3
Output mode
→ For a detailed description of the output mode (BFM#0), refer to Subsection 5.4.1.
-32MT-LT(-2) PLC, the unit numbers from 1 to 7
3UC
-4DA.
3U
Unit
number: 1
Input/output
Special
extension
function block
block
ch1
ch2
Analog output range
Digital input range
-10 V to +10 V
-32000 to +32000
-10 V to +10 V
-10000 to +10000
0 mA to 20 mA
4 mA to 20 mA
0 mA to 20 mA
4 Analog Output
4.1 Analog Output Procedures
-4DA.
3U
Unit
number: 2
Special
function unit
0 to 32000
0 to 32000
0 to 20000
E-13
A
B
C
D
E
F
G
H
I
J