5.4.23 BFM#127: Abrupt change detection status data automatic transfer-to data register
specification
Use this function to automatically transfer the abrupt change detection status data (BFM#27) to the data
register specified in BFM#127.
When abrupt change is detected, data will be automatically transferred from the 4AD to the PLC. For this
reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
shortened.
1. If "BFM#127 = K209 (initial value)"
Specified data register
D209
2. Caution regarding abrupt change detection status data automatic transfer to data register
specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the abrupt change detection status data automatic transfer function (b6 of BFM#22) and
the abrupt change detection function (b2 of BFM#22).
• The data written to BFM#127 will be retained in the EEPROM.
3. Caution regarding EEPROM writing
If data is written to BFM#0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
B-44
PLC User's Manual - Analog Control Edition
3UC
→ For a detailed description of the abrupt change detection status data (BFM#27),
Abrupt change detection status data in BFM#27
Description
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
Setting range: 0 to 7999
Initial value (at delivery) : K209
Numeric data type: Decimal (K)
refer to Subsection 5.4.10.