Start-Up Cycle Diagnostics; Resetting The Control Box And Using Diagnostics - Riello 40 GS10 Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

Available languages

Available languages

4.5

Start-up cycle diagnostics

During start-up, indication is according to the following table:
Sequences
Pre-purging
Ignition phase
Operation, flame ok
Operating with weak flame signal.
Electrical supply lower than
Lock-out
Extraneous light
Index:
Off
4.6

Resetting the control box and using diagnostics

The control box features a diagnostics function through which any causes of malfunctioning are easily identi-
fied (indicator: RED LED).
To use this function, you must wait at least 10 seconds once it has entered the safety condition (lock-out),
and then press the reset button.
The control box generates a sequence of blinks (1 second apart), which is repeated at constant 3-second
intervals.
Once you have seen how many times the light blinks and identified the possible cause, the system must be
reset by holding the button down for between 1 and 3 seconds.
RED LED on
wait at least 10s
The methods that can be used to reset the control box and use diagnostics are given below.
RESETTING THE CONTROL BOX
To reset the control box, proceed as follows:
Hold the button down for between 1 and 3 seconds. 
The burner restarts after a 2-second pause once the button is released.
If the burner does not restart, you must make sure the limit thermostat is closed.
VISUAL DIAGNOSTICS
Indicates the type of burner malfunction causing lock-out.
To view diagnostics, proceed as follows:
Hold the button down for more than 3 seconds once the red LED (burner lock-out) remains steadily lit.
A yellow light blinks to tell you the operation is done.
Release the button once the light blinks. The number of times it blinks tells you the cause of the malfunc-
tion, indicated in the table below.
SOFTWARE DIAGNOSTICS
Reports the life of the burner by means of an optical link with the PC, indicating hours of operation, number
and type of lock-outs, serial number of control box etc ...
To view diagnostics, proceed as follows:
Hold the button down for more than 3 seconds once the red LED (burner lock-out) remains steadily lit. 
A yellow light blinks to tell you the operation is done.
Release the button for 1 second and then press again for over 3 seconds until the yellow light blinks again.
Once the button is released, the red LED will flash intermittently with a higher frequency: only now can the
optical link be activated.
COLOUR CODE TABLE
~
170V
Yellow
Lock-out
Green
Red
Press reset
for > 3s
Blinks

9
GB
Colour code
Interval
3s
Blinks

20008491