OPERATING PROCEDURE
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels (refer to section 1).
(2) Remove the inverter assembly (refer to section 2).
(3) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor.
(5) Remove the compressor nuts.
(6) Remove the compressor.
(7) Detach the brazed part of pipes connected with 4-way valve.
OCH796A
(0 MPa).
2
PHOTOS/FIGURES
Photo 10
Suction pipe
brazed part
43
Discharge pipe
brazed part
Brazed parts of 4-way valve