Mitsubishi Electric SUZ-SWM30VA TH Series Service Manual page 42

Outdoor/indoor unit hfc utilized r32
Table of Contents

Advertisement

OPERATING PROCEDURE
3. Removing R. V. coil
(1) Remove the cabinet and panels (refer to section 1).
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
4. Removing the discharge temperature thermistor,
defrost thermistor, outdoor heat exchanger tempera-
ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels (refer to section 1).
(2) Disconnect the lead wire to the reactor and the following
connectors:
<Inverter P.C. board>
CN641 (Defrost thermistor and discharge temperature ther-
mistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
5. Removing outdoor fan motor
(1) Remove the cabinet and panels (refer to section 1).
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931, CN932 (Fan motor)
(3) Remove the propeller fan nut.
(4) Remove the propeller fan.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.
OCH796A
PHOTOS/FIGURES
Photo 7
Screw of the
R.V. coil
Discharge
temperature
thermistor
Compressor
protector
Figure 1
Attach the compressor
protector to the
protector holder with the
surface on which the
model name is printed
facing the area hatched
in the figure.
Photo 8
Outdoor heat ex-
changer temperature
thermistor
Photo 9
Screws of the outdoor fan motor
Propeller fan
42
Ambient temperature
thermistor
Defrost thermistor
Propeller fan nut