Install The Connecting Pipe - Bosch CLIMATE 5000 VRF RDCI Series Installation & User Manual

Switch box
Hide thumbs Also See for CLIMATE 5000 VRF RDCI Series:
Table of Contents

Advertisement

6.

INSTALL THE CONNECTING PIPE

6.1.
Range of SBOX application
Table: 6-1
SBOX outside
Model
drawing
SBOX01
SBOX02
SBOX04
SBOX06
SBOX02E
SBOX04E
6.2.
Connecting diagram of SBOX and indoor unit
Table: 6-2
Connecting diagram 1
indoor unit
max:4 units, max capacity:16kW
max:4 units, max capacity:16kW
indoor unit
max:4 units, max capacity:16kW
indoor unit
max:4 units, max capacity:16kW
indoor unit
max:4 units, max capacity:16kW
indoor unit
max:4 units, max capacity:16kW
indoor unit
Suitable model
SBOX01
1. Capacity matching with each indoor unit group is lower
than16kW.
Note
2. If auto mode function has been disabled, you may con-
nect up to four indoor units on one port. If auto mode has
been selected, only one indoor unit per port is allowed.
CLIMATE 5000 VRF
Max. connecting
Max. total indoor
indoor unit quantity
unit capacity
4×1=4
16kW
4×2=8
28kW
4×4=16
45kW
4×6=24
45kW
1
28kW
1
56kW
total max capacity:
16kW(for SBOX01)
28kW(for SBOX02)
45kW(for SBOX04/06)
SBOX02
SBOX04
SBOX06
Connecting diagram 2
Suitable model
Match with large capacity duct type unit
Note
(20.0kW~28.0kW)
Connecting diagram 3
indoor unit
Suitable model
Match with large capacity duct type unit
Note
(40.0kW~56.0kW)
Note: for pipe sizing guidelines and connections to SBOX, refer to
outdoor unit installation manual.
CAUTION
• Do not let air, dust, or other impurities fall in the pipe system during instal-
lation.
• Keep the connecting pipe dry, and do not let moisture in during installation.
• Ensure you insulate copper pipes with a minimum of 10mm thick. For high
humidity and warm locations, use thicker insulation.
INSTALL THE CONNECTING PIPE | 7
max: 1 unit, max capacity: 28kW
indoor unit
SBOX02E
max: 1 unit, max capacity:56kW
SBOX04E
6720862460 (16/04)