L3-00 - Outdoor Unit: Electrical Box Temperature Rise Problem - Daikin EBLA04E V Series Service Manual

Table of Contents

Advertisement

3
|
Troubleshooting
3.3.64 L3-00 – Outdoor unit: Electrical box temperature rise problem
Service manual
62
draft – 31/05/2022 15:53
1 Check if the power supply is compliant with the regulations. See
4
circuit" [
 254].
Possible cause:
▪ Faulty or disturbance of the power supply (power supply MUST be within
range of nominal operating voltage ±4%),
▪ Power drop,
▪ Short circuit.
2 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Switch box temperature is
too high.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
2 Perform a check of the outdoor unit fan motor. See
4
motor" [
 197].
Possible cause: Faulty outdoor unit fan motor.
3 Check if the power supply is compliant with the regulations. See
4
circuit" [
 254].
Possible cause:
▪ Faulty or disturbance of the power supply (power supply MUST be within
range of nominal operating voltage ±4%),
▪ Power drop,
▪ Short circuit.
4 Clean the outdoor heat exchanger. See "6 Maintenance" [
Possible cause: Dirty outdoor heat exchanger.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
"4.14 Main
Effect
Unit will stop operating.
"4.14 Main
"5.1 Electrical
4
PCB" [
 184].
Reset
Manual reset via remote
controller.
4
PCB" [
 184].
"4.15  Outdoor unit fan
"5.1 Electrical
4
 275].