Ekip Touch - Settings; Main Settings - ABB SACE Emax 2 Instructions Manual

Emax low voltage air circuit-breakers e1.2-e2.2-e4.2-e6.2
Table of Contents

Advertisement

Ekip Touch - Settings

1 - Main settings

Foreword All the following parameters are available either directly, or from the Settings menu, in the conditions
Configuration The Circuit breaker-Configuration menu, allowing the presence of the External neutral sensor to be
Ground protection In the earth Circuit-breaker-Protections menu of the LSIG version of Ekip Touch you can:
Line frequency Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and
26 | © 2023 ABB | 1SDH001316R1002 - ECN000297030
established by Ekip Touch on the basis of the version and configuration described.
1SDH001330R1002
Consult manual
and for the Integrative settings (available by accessing the unit by means of a service connector via Ekip
Connect or by communication via system bus):
• Circuit-breaker: Hardware Trip, T Protection, Neutral Protection
• Phase Sequence
• Monitor time
• Power Controller
• Load Shedding
• Network Analyzer
• Datalogger
• Dual Set
• Functions
• View
• Maintenance
• Programmable states
• Filters
• TAG Name, User data, Clients Page
• LED Alive
• Supplementary settings for commands, zone selectivity, Wizard
WARNING! changes to the settings must be made in the absence of protection alarms
activated, is available for the 3P CB.
Activation of the configuration with External neutral (3P + N) enables:
• histograms of phase Ne in the Histograms page
• neutral current measurements
• submenu for configuring the Neutral protection ( Neutral Protection )
• neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
• activate/deactivate the presence of external toroid S.G.R and relative Gext protection.
• activate the presence of Rc Toroid and relative protection.
• activate/deactivate the MDGF transformer presence and relative MDGF protection.
NOTE: Rc Toroid can be activated if the Measuring Measurements package and Rc version
Rating plug are present; Toroid presence in the menu can only be deactivated afterwards
by replacing the installed Rating plug
With Ekip Touch LSIG, the parameter is set by default as: Absent.
60 Hz.
NOTE: the measurements are taken on the basis of the set grid frequency: incorrect
configuration of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.
for any Main settings in the menu which are not described below
ABB | SACE Emax 2
Ekip Touch - Settings
1 - Main settings