Ekip Touch - Measurements; Class 1 Power & Energy Metering - ABB SACE Emax 2 Instructions Manual

Emax low voltage air circuit-breakers e1.2-e2.2-e4.2-e6.2
Table of Contents

Advertisement

Ekip Touch - Measurements

1 - Class 1 Power & Energy Metering
List and performance Presence of the Class 1 Power & Energy Metering package allows higher measuring accuracy to be
Functional characteristics The measuring performance of the Class 1 Power & Energy Metering package is guaranteed in the
Information page Presence of the Class 1 Power & Energy Metering package activates the IEC 61557-12 information page,
25 | © 2023 ABB | 1SDH001316R1002 - ECN000297030
obtained for the following quantities:
Measurement
Monitor time (min-max)
Phase currents
0,004 ÷ 64 In
(6) (8)
Internal earth fault
0,08 ÷ 64 In
current
(2)
Line frequency
30 ÷ 80 Hz
Total active and
|Pmin ÷ Pmax|
apparent power
(7)
Active and apparent
|Pmin ÷ Pmax|
phase power
Total active and
1 kWh ÷ 2 TWh; 1 kVARh ÷ 2 TVARh;
apparent energy
1 kVAh ÷ 2 TVAh
Power factor
0,5 ÷ 1
(1)
the accuracy values refer to the normal operating intervals and conditions established by IEC
61557-12, for each quantity and class declared
(2)
available with LSIG versions
(3)
available for voltage values of over 30 V (with Un < 277 V) or 60 V (with Un ≥ 277 V)
(4)
47 ÷ 55 Hz with fn = 50 Hz; 54 ÷ 66 Hz with fn = 60 Hz
Pmin = 0,5 In x 5 V; Pmax= 3 x 16 In x 900 V
(5)
the higher phase currents are also available in the Histograms, Measuring instruments and
(6)
Measurement summary pages
the higher total powers are also available in the Measuring instruments and Measurement
(7)
summary pages
internal phase current; in the presence of an external Neutral, the accuracy of current Ne is 1%
(8)
following conditions (from table 43 of standard IEC 61557-12):
Characteristic
Classification of performance measuring and
monitoring device (PMD) in accordance with chapter
4.3 of the standard
Temperature
humidity and altitude
Performance class for active energy and power
which can be consulted in the About menu
Figure 9
The page shows the activation state of the Class 1 Power & Energy Metering package ( Activated /
Deactivated ) and the serial numbers of certain accessories installed on the CB for the specific purpose of
conforming to the characteristics of the package (electronic units and internal current sensors)
Normal operating
range
Standard IEC 61557-12,
tables 20-22
Standard IEC 61557-12,
table 20
fn ± 10 %
(3)
Standard IEC 61557-12,
(5)
tables 8-11-14
Standard IEC 61557-12,
(5)
tables 8-11-14
Standard IEC 61557-12,
tables 8-11-14
Standard IEC 61557-12,
table 27
Value
PMD-DD
Operating: T= -25°C to +70°C; Storage: T =
-30°C to +70°C; Class: K70
Up to 90% relative humidity without
condensation; From 0 to 2000 meters
1
ABB | SACE Emax 2
Accuracy of
read value
0,5 %
(1)
0,5 %
(1)
± 0,02 Hz
(4)
1 %
(1)
1 %
(1)
1 %
(1)
1%
(1)
Ekip Touch - Measurements
1 - Class 1 Power & Energy Metering

Advertisement

Table of Contents
loading

Table of Contents