8
|
Piping installation

8.6.6 To fill the heat exchanger inside the storage tank

8.6.7 To fill the storage tank

Installer reference guide
118
5 Fill the system with water until the external manometer shows that the
system target pressure is reached (system height +2 m; 1 m water column =
0.1 bar). Make sure that the pressure relief valve does not open.
6 Close the manual air vent valves as soon as water emerges free of bubbles.
7 Close the water tap. Keep the fill and drain valve open in case it is necessary to
repeat the filling procedure after the air purging of the system. See
4
purge
function" [
8 Close the fill and drain valve and remove the hose with non-return valve only
after air purging is performed and the system is completely filled.
Following heat exchanger have to be filled with water before the storage tank can
be filled:
The domestic hot water heat exchanger
NOTICE
To fill the domestic hot water heat exchanger, use a field supply filling kit. Make sure
you comply with the applicable legislation.
1 Open the shut-off valve for the cold water supply.
2 Open all hot water taps in the system to make sure that the tapped water flow
is as high as possible.
3 Keep the hot water taps open and the cold water supply running until no
more air is vented from the taps.
4 Check for water leaks.
The bivalent heat exchanger (only for some models)
5 Fill the bivalent heat exchanger with water by connecting the bivalent heating
circuit. If the bivalent heating circuit will be installed on a later stage, fill the
bivalent heat exchanger with a filling hose until water comes out of both
connections.
6 Do air purge on the bivalent heating circuit.
7 Check for water leaks.
NOTICE
Before the storage tank can be filled, the heat exchangers inside the storage tank
have to be filled, see previous chapters.
Fill the storage tank with a water pressure <6 bar and a flow speed <15 l/min.
Without installed drainback solar kit (option)
1 Connect a hose with non-return valve (1/2") to the drainback connection.
2 Fill the storage tank until water spills from the spillover connection.
3 Remove the hose.
 254].
"12.4.2 Air
ERLA11~16D + EBSH/X(B)11+16P30+50D
Daikin Altherma 3 R ECH₂O
4P663482-1C – 2023.05