Setup
A Main leaving water temperature zone
B Room 1
C Room 2
a Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
▪
For more information about connecting the electrical wiring to the unit, see:
-
"9.2 Connections to the outdoor
-
"9.3 Connections to the indoor
▪
The underfloor heating of the main room is directly connected to the indoor unit.
▪
The room temperature of the main room is controlled by the dedicated Human
Comfort Interface (BRC1HHDA used as room thermostat).
▪
A thermostatic valve is installed before the underfloor heating in each of the
other rooms.
INFORMATION
Mind situations where the main room can be heated by another heating source.
Example: Fireplaces.
Configuration
Setting
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
Benefits
▪
Easy. Same installation as for one room, but with thermostatic valves.
B
C
a
T
A
4
unit" [
125]
4
unit" [
129]
2 (Room thermostat): Unit operation
is decided based on the ambient
temperature of the dedicated Human
Comfort Interface.
0 (Single zone): Main
ERLA11~16D + EBSH/X(B)11+16P30+50D
Value
Daikin Altherma 3 R ECH₂O
4P663482-1C – 2023.05