Advertisement

Diagnostics and troubleshooting
10.5 Treatment of measurement errors
Text message
with the main
controller
M511
Inconsistent
software
configuration
10.5

Treatment of measurement errors

The tables below give typical examples of application-related measurement errors.
The images in column ""Error description" show the actual level as a dashed line and
the output level as a solid line.
1
2
Figure 10.2
Note
If the output level is constant, the cause could also be the fault setting of the current
output to ""Hold value".
If the level is too low, the reason could be a line resistance that is too high
Measured value shows a
too low or too high level
Measured value jumps
towards 100 %
40
Code
A software unit requires a
software update
Real level
Level displayed by the transmitter
Treatment of measurement errors
Fault description
Min./max. adjustment not correct
Incorrect linearization curve
Due to the process, the amplitude
of the level echo sinks
A auto false echo suppression was
not carried out
Cause
Carry out software update
Cause
Rectification
State in CMD 48
Bit 11 of
Byte 14 ... 24
Rectification
Adapt min./max. adjustment
Adapt linearization curve
Carry out a auto false echo
suppression