ABB Ekip Touch Operating Instructions Manual page 17

Protection settings setup for touch trip units

Advertisement

P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S
A DJ U S T I N G T H E I N S TA N TA N E O U S P R O T E C T I O N S E T T I N G S
Factory Default Settings
Protection Function
Frame
XT5
Instantaneous Protection
I Protection Short Circuit
XT7/XT7M
(50)
Emax 2
Range Adjustability
Protection Function
Frame
XT5
Instantaneous Protection
XT7/XT7M
I Protection Short Circuit (50)
Emax 2
I3 threshold must be higher than I2 (if S Enabled = ON)
2
Step 23. Press I Protection Short circuit (50) row
A DJ U S T I N G T H E I N S TA N TA N E O U S P I C K U P O R T H R E S H O L D I 3
Step 24. Press the Threshold I3 4.0 in row
Function /
Enabled
Trip Enabled
Curve
ON
-
-
Threshold / Pickup Range
1.5 x In to 15 x In; in 0.1 In steps
Threshold /
Time /
Pickup
Delay
I3 = 4 x In
-
2
17
Thermal
Pre-alarm
Memory
-
-
Time / Delay Range
-
23
24