P R OT E C T I O N S E T T I N G S S E T U P F O R E K I P TO U C H T R I P U N I T S
15
Step 19. Change the Short Time Pickup / Threshold I2 setting to the value in the coordination study.
The setting range is from 0.6 to 10.0 of the breaker's nominal rating (rating plug value)
Press the minus icon or the plus icon to change to the value in the coordination study (maintaining the
press will advance the settings faster). Then press Confirm
NOTE: The value is given as both absolute value (Amperes) and in relative value (In) and can be set within the range: 0.6 In to 10 In, in steps of 0.1 In